2026-0045 Nusantara Nickel Smelter, E-House and LV distribution package
C3Accept

Engineering ontology

The controlled vocabulary the extraction schema is generated from. Attributes carry a canonical unit, an accepted set of values, a plausibility envelope and the surface forms they appear as in tender documents.

SRS section 6, ontology and units. Pinned version lv-panel/1.3.0

Attributes defined

26

Version lv-panel/1.3.0

Medium criticality

8

High criticality

9

Critical criticality

5

Attribute definitions
Select a row to inspect its full definition.
KeyLabelKindUnitCriticality
RatedVoltageRated operational voltage (Ue)numericVCritical
RatedFrequencyRated frequencynumericHzMedium
RatedCurrentMainRated current of the main busbar (InA)numericACritical
ShortCircuitWithstandIcwRated short-time withstand current (Icw)numerickACritical
ShortCircuitDurationRated duration of short circuitnumericsHigh
PeakWithstandIpkRated peak withstand current (Ipk)numerickAHigh
IPRatingDegree of protection (IP)enum-High
IKRatingDegree of protection against mechanical impact (IK)enum-Low
FormOfSegregationForm of internal separationenum-High
BusbarMaterialBusbar materialenum-High
BusbarPlatingBusbar platingenum-Medium
EnclosureMaterialEnclosure materialenum-Medium
SheetThicknessEnclosure sheet thicknessnumericmmMedium
PaintColourFinish colourenum-Low
CableEntryDirectionCable entry directionenum-High
ProtocolCommunication protocolenum-High
EarthingSystemSystem earthing arrangementenum-High
NeutralBusbarRatingNeutral busbar ratingenum-Medium
ArcContainmentInternal arc classificationenum-Critical
AmbientTemperatureMaxMaximum ambient temperaturenumericCelHigh
RelativeHumidityMaxMaximum relative humiditynumeric%Low
AltitudeMaxInstallation altitudenumericmMedium
PollutionDegreePollution degreeenum-Medium
MountingTypeMounting arrangementenum-Low
SurgeProtectionTypeSurge protection device typeenum-Medium
StandardComplianceGoverning assembly standardenum-Critical
Rated operational voltage (Ue)
Line-to-line operational voltage of the main busbar system. Drives clearance, creepage and device selection.
Key
RatedVoltage
Value kind
numeric
Canonical unit
V
Criticality
Critical
Accepted units
V (x1), kV (x1000)
Plausibility envelope
100 to 1000 V

Typical band 220 to 690.

Standard reference
IEC 61439-1 clause 5.2.1

Surface forms recognised

rated voltageoperating voltagesystem voltagenominal voltagetegangan nominaltegangan kerjaUe

Both English and Bahasa Indonesia forms are held, because tender packages in this market mix the two inside a single clause.

Normalisation
Type a value as it might appear in a document. The canonical form is derived, the original is always kept, and an out-of-envelope value is flagged rather than corrected.
The ontology version is pinned and travels with every claim. If a definition changes, claims produced under the old version are still readable against the definition that produced them, which is what makes a correction set meaningful later.