Acting as EngineerC3Accept
Requirement compliance matrix
Every requirement against what the engineering actually proposes, and the evidence that closes the gap between the two. Nothing here is stored: the matrix is recomputed from the record, so it cannot fall out of step with the records it summarises.
Master prompt section 30, compliance AI
Requirements
12
0 not applicable.
Proven compliant
0
Canonical value, recorded solution and a passing deterministic check.
Not proven
12
Anything that is not COMPLY. Not the same as failing.
Not compliant
0
The proposed solution contradicts the canonical value with no approved deviation.
A requirement reaches COMPLY only when three things exist together: a canonical value, a proposed solution recorded in the configuration snapshot, and a deterministic checker that has passed on that item. A value that matches but has never been checked stops at PARTIAL COMPLY. The default is not compliance, because a matrix that assumes compliance until contradicted is a matrix that reports the absence of checking as success.
Status distribution
Filter the register below.
Compliance register
Select a row to see the evidence chain behind its status.
| Reference | Requirement | Type | Criticality | Canonical | Proposed | Status | Confidence |
|---|---|---|---|---|---|---|---|
| SPC 3.1 | All assemblies shall be design verified and shall comply with IEC 61439-2 in full. | mandatory | Critical | IEC61439-2 | IEC61439-2 | Partial comply | medium |
| SPC 3.2 a | The main busbar system shall be rated 400 V, three phase, four wire, 50 Hz. | mandatory | Critical | 400 V | 400 | Partial comply | medium |
| SPC 3.2 c | Each assembly shall withstand a short circuit of 65 kA for 1 s. | mandatory | Critical | 65 kA | 65 | Partial comply | medium |
| SPC 3.3 a | Internal separation shall be Form 4b throughout. | mandatory | High | Form4b | Form4b | Partial comply | medium |
| SPC 3.3 b | Busbars shall be electrolytic grade copper, silver plated at every bolted joint. | mandatory | High | COPPER | COPPER | Partial comply | medium |
| SPC 3.4 a | The degree of protection shall be IP54 with all doors closed and all cable entries sealed. | mandatory | High | IP54 | IP54 | Partial comply | medium |
| SPC 3.4 b | Cable entry shall be from the bottom throughout the switchroom. | mandatory | High | BOTTOM | BOTTOM | Partial comply | medium |
| SPC 3.4 c | The system earthing arrangement is TN-S with a full rated neutral busbar. | optional | High | TN-S | TN-S | Partial comply | medium |
| SPC 3.2 b | The rated current of the main horizontal busbar shall be not less than 4000 A continuous. | mandatory | Critical | none | none | Unknown | none |
| SPC 3.5 | Each assembly shall provide a Modbus TCP interface for metering, breaker status and trip annunciation. | mandatory | High | MODBUS_TCP | none | Unknown | none |
| SPC 3.6 | The design ambient temperature shall be 65 C. | mandatory | High | none | none | Unknown | none |
| SPC 3.7 | The assembly shall provide adequate protection for operating personnel in the event of an internal arcing fault. | mandatory | Critical | none | none | Unknown | none |