2026-0045 Nusantara Nickel Smelter, E-House and LV distribution package
C3Accept

MCC-01 Motor control centre, ore handling

Configured item CFG-2026-0045-0002, product family LV_PANEL, upstream configuration CONF-88240.

SRS section 7.2, configuration drift control

draft

Snapshot revision

1

Revision captured into the record.

Upstream revision

1

Current revision in the configurator.

Drift status

in sync

Last checked 2026-05-17 08:00

Engineering objects

1

Objects depicted on the design documents.

Snapshot record
Everything needed to reproduce what was released, without asking the configurator again.
Snapshot identifier
SNP-2026-0045-0002
Configuration
CONF-88240
Configuration revision
1
Payload hash
2bdf10bb19d5
Producing application version
cfg-4.7.2

Recorded so a configurator upgrade that changes payload semantics is detectable.

Captured
2026-05-08 13:00 by Dewi Anggraini
Drift status
In sync
Last checked
2026-05-17 08:00
Configured attributes
Read from the stored payload, resolved against the ontology.
AttributeKeyValueCriticality
Rated operational voltage (Ue)RatedVoltage400 VCritical
Rated frequencyRatedFrequency50 HzMedium
Rated current of the main busbar (InA)RatedCurrentMain2500 ACritical
Rated short-time withstand current (Icw)ShortCircuitWithstandIcw50 kACritical
Rated duration of short circuitShortCircuitDuration1 sHigh
Rated peak withstand current (Ipk)PeakWithstandIpk110 kAHigh
Degree of protection (IP)IPRatingIP54High
Degree of protection against mechanical impact (IK)IKRatingIK08Low
Form of internal separationFormOfSegregationForm4aHigh
Busbar materialBusbarMaterialCOPPERHigh
Busbar platingBusbarPlatingSILVERMedium
Enclosure materialEnclosureMaterialMILD_STEELMedium
Enclosure sheet thicknessSheetThickness2 mmMedium
Finish colourPaintColourRAL7035Low
Cable entry directionCableEntryDirectionBOTTOMHigh
Communication protocolProtocolMODBUS_TCPHigh
System earthing arrangementEarthingSystemTN-SHigh
Neutral busbar ratingNeutralBusbarRating100_PERCENTMedium
Internal arc classificationArcContainmentIAC_A_FLCritical
Maximum ambient temperatureAmbientTemperatureMax50 CelHigh
Mounting arrangementMountingTypeFLOOR_STANDINGLow
Surge protection device typeSurgeProtectionTypeTYPE2Medium
Governing assembly standardStandardComplianceIEC61439-2Critical
Pollution degreePollutionDegree3Medium