2026-0045 Nusantara Nickel Smelter, E-House and LV distribution package
C3Accept

DB-EH-01 E-House auxiliary distribution board

Configured item CFG-2026-0045-0003, product family LV_PANEL, upstream configuration CONF-88252.

SRS section 7.2, configuration drift control

draft

Snapshot revision

1

Revision captured into the record.

Upstream revision

1

Current revision in the configurator.

Drift status

in sync

Last checked 2026-05-17 08:00

Engineering objects

1

Objects depicted on the design documents.

Snapshot record
Everything needed to reproduce what was released, without asking the configurator again.
Snapshot identifier
SNP-2026-0045-0003
Configuration
CONF-88252
Configuration revision
1
Payload hash
0df255bd9e93
Producing application version
cfg-4.7.2

Recorded so a configurator upgrade that changes payload semantics is detectable.

Captured
2026-05-08 17:00 by Fajar Nugroho
Drift status
In sync
Last checked
2026-05-17 08:00
Configured attributes
Read from the stored payload, resolved against the ontology.
AttributeKeyValueCriticality
Rated operational voltage (Ue)RatedVoltage400 VCritical
Rated frequencyRatedFrequency50 HzMedium
Rated current of the main busbar (InA)RatedCurrentMain630 ACritical
Rated short-time withstand current (Icw)ShortCircuitWithstandIcw35 kACritical
Rated duration of short circuitShortCircuitDuration1 sHigh
Rated peak withstand current (Ipk)PeakWithstandIpk73 kAHigh
Degree of protection (IP)IPRatingIP54High
Degree of protection against mechanical impact (IK)IKRatingIK08Low
Form of internal separationFormOfSegregationForm2bHigh
Busbar materialBusbarMaterialCOPPERHigh
Busbar platingBusbarPlatingSILVERMedium
Enclosure materialEnclosureMaterialMILD_STEELMedium
Enclosure sheet thicknessSheetThickness2 mmMedium
Finish colourPaintColourRAL7035Low
Cable entry directionCableEntryDirectionBOTTOMHigh
Communication protocolProtocolNONEHigh
System earthing arrangementEarthingSystemTN-SHigh
Neutral busbar ratingNeutralBusbarRating100_PERCENTMedium
Internal arc classificationArcContainmentNONECritical
Maximum ambient temperatureAmbientTemperatureMax50 CelHigh
Mounting arrangementMountingTypeWALL_MOUNTEDLow
Surge protection device typeSurgeProtectionTypeTYPE2Medium
Governing assembly standardStandardComplianceIEC61439-2Critical
Pollution degreePollutionDegree3Medium